Apollo XP95 Intelligent Open-Area Sounder/Indicator with Isolator (55000-005)
  • Multiple functions at one location
  • Self-test fault monitoring
  • Individual control of the sounder and visual indicator
  • Tones may be used for other purposes than warning of fire
  • Soft start option, ideal for hospitals and nursing homes
View all

At a glance

General

The AS996I is a 990 series, intelligent loop powered open-area sounder/beacon in RED with a built in isolator. It is designed for use in indoor applications. It supports 15 evacuation and 15 alert tones with volume settings that are adjustable from the CIE. A locking mechanism is included to prevent unauthorized removal of the AS996I from its base.

Isolation and Maintenance

The AS996I sounder/beacon is supplied with an isolating base. A yellow LED on the base is illuminated if a loop short circuit is detected. All fault and abnormal conditions such as sounder and/or beacon failures are reported back to the panel for easy fault finding.

Sounder Tone and Volume Support

The AS996I offers a choice of 15 evacuation and 15 alert tones. Two tones may be selected during installation, one for evacuation and one for alert. Volume levels may be selected during commissioning to one of 7 pre-set levels, with output ranging from 60 dB(A) to 100 dB(A). The low volume range is useful in areas such as hospitals where the alert is initially intended to warn staff only. Becayse tones can be used for other purposes in addition to warning of fire, it makes the AS996I ideal for use in schools etc.

During commissioning the sounder volume can be adjusted on location without disassembly or removal. With the CIE in "setup" mode, the commissioning engineer is able to adjust the volume using a magnetic wand. Once all sounders have been adjusted, "setup" mode on the CIE is cancelled and all sounder volume levels are stored in the sounder.

Beacon

The AS996I incorporates a RED beacon with a flash rate of 1 Hz. The beacon can be separately controlled from the sounder, programmable from the CIE.

Details

  • Multiple functions at one location
  • Self-test fault monitoring
  • Individual control of the sounder and visual indicator
  • Tones may be used for other purposes than warning of fire
  • Soft start option, ideal for hospitals and nursing homes
  • Volume and tone settings can be selected from the control panel
  • Group and global control for increased response time
  • Self-test fault monitoring
  • Alarm synchronisation
  • Loop powered
  • Including loop isolator

Technical specifications

General
Compatibility
Apollo protocol systems
Addressing method
DIL switch
Monitoring
Activated
Device removal
Fault
Electrical
Power supply type
Loop powered
Operating voltage
17 to 28 VDC
Current consumption
Quiescent: 330 µA at 24 VDC
Switch on surge (<1s): 1.2 mA at 24 VDC
Alarm (Sounder/Beacon max. volume): 8.2 mA at 24 VDC
Alarm (Sounder only): 5.1 mA at 24 VDC
Alarm (Beacon only): 3.1 mA at 24 VDC
Number of connection terminals
5
Sounder
Output level
100 dB(A) @ 90° ± 3dB(A) (tone dependant)
Output level adjustment
2 Levels
Frequency
Tone dependant
Selectable tones
3
VID
Colour
Red
Flash frequency
1 Hz
Synchronization
Supported
Physical
Physical dimensions
97.5 x 104 mm (d x dia)
Net weight
260 g
Colour
Red
Mounting type
Base mount
Mounting position
Ceiling
Wall
Mounting base
Deep
Material
Moulded polycarbonate
Texture
Smooth
Environmental
Vandal proof
No
Operating temperature
-10 to +55°C
Relative humidity
0 to 95% noncondensing
Environment
Indoor
Outdoor
IP rating
IP65
Regulatory
Compliancy
CE
REACH
RoHS 3
WEEE
Certification
CPR
Standards
EN54-3